Fire ratings for acoustic panels: what Class A does and does not cover

Acoustic panel fire rating explained: how IBC Chapter 8 reads ASTM E84 classes, when fabric faces need NFPA 265 or 286, and why tests must match the install.

A charcoal felt oven mitt gripping the top of a three-layer felt sandwich in olive, oat and rose clay, with the lower layers sticking out below the mitt.
Reader question
Is a Class A (ASTM E84) rating enough for fabric-wrapped or felt panels on walls and ceilings, or does the code ask for more?

A Class A rating under ASTM E84 is often enough, but only when the report covers the panel as built (core, face, adhesive and mounting), the code route for your material accepts an E84 result, and Class A meets what the room requires. Fabric faces can pull a panel into the International Building Code’s textile wall covering rules: test in the manner intended for use, then pass a room-corner test (NFPA 265 or NFPA 286) or reach Class A with automatic sprinklers. Many rooms need less than Class A; a fabric-faced panel on a wall can need more than an E84 index alone.

This article reads Chapter 8 of the 2021 IBC the way a plan reviewer does, using the text as published in Seattle’s adopted code, and explains what each document in a fire submittal proves. It is written for architects, interior designers, contractors and owners of commercial spaces. Which edition applies to your building, and how a given panel is classified, is decided by your local building official, not by a data sheet.

What ASTM E84 measures, and what it leaves out

ASTM E84 is a 10-minute tunnel test that compares how fast flame spreads across a material’s surface, and how much smoke it gives off, against reference materials. It reports two numbers, a flame spread index and a smoke-developed index. It does not show how a whole room of that material behaves in a fire.

The scope of ASTM E84 describes a “comparative surface burning behavior” test “applicable to exposed surfaces such as walls and ceilings.” The specimen is about 24 ft long and 20 in wide and sits in the ceiling position of the tunnel, face down to the burner. The standard says it provides “only comparative measurements” against select grade red oak and fiber-cement board, with the air flow and flame adjusted so flame runs the full length of the red oak in 5 1/2 minutes. ASTM’s store lists E84-26a as the active edition.

What the test does not tell you

Section 4.3 lists what E84 does not provide, and one item matters for acoustic panels: “the effect of aggravated flame spread behavior of an assembly resulting from the proximity of combustible walls and ceilings.” A room lined with panels on several walls is exactly that kind of assembly. Section 1.8 adds that the method “does not by itself incorporate all factors required for fire-hazard or fire-risk assessment.” That gap is why codes also recognize room-corner tests.

Three warnings in the scope

  • Supports change results. Section 1.4: supporting materials on the underside of a specimen can lower its flame spread index, and the results “do not necessarily relate” to the same material tested without support.
  • Melting changes results. Section 1.5: materials that “melt, drip, or delaminate” can produce low flame spread indices “that do not relate directly” to materials that stay in place. Ask whether the lab noted melting or dripping for any core or face that can soften.
  • The two indices are separate. Section 1.3: “there is not necessarily a relationship between these two measurements.” A low flame spread does not imply low smoke.

E84 and UL 723

The IBC accepts results from ASTM E84 or UL 723 for the classes in 803.1.2, and specifications often cite both. The VA template, for example, lists UL 723 as the “Test for Surface Burning Characteristics of Building Materials” beside E84. Treat a UL 723 report the way you would an E84 report: check the specimen, the mounting and the edition.

For materials that need a longer exposure, E84 points to ASTM E2768, a 30-minute extended version of the tunnel test. That standard comes up again with fire-retardant coatings below.

How the IBC turns E84 indexes into classes

The IBC sorts E84 results into Classes A, B and C by flame spread, with the same smoke limit for all three. It also lets a material that passes the NFPA 286 room-corner test count as Class A. Acoustic panels are interior finish under the code, so these rules apply to them.

Section 803.1.2 of the 2021 IBC, as published in the 2021 Seattle Building Code, Chapter 8, sets the classes:

Class Flame spread index Smoke-developed index
A 0 to 25 0 to 450
B 26 to 75 0 to 450
C 76 to 200 0 to 450

Section 803.1.1 says materials meeting the NFPA 286 acceptance criteria “shall be considered to also comply with the requirements of Class A.” Section 803.13 confirms that such materials may be used wherever Class A is required.

Reading the two numbers together

The class comes from the flame spread index, but every class also carries the same smoke ceiling of 450. A hypothetical product with a flame spread index of 20 and a smoke-developed index of 500 is not Class A, B or C; it fails all three on smoke. So read both numbers on every report, and do not accept a letter grade without the indices behind it.

Why panels count as interior finish

The code is explicit. Section 806.2 says “paneling, wall pads and crash pads applied structurally or for decoration, acoustical correction, surface insulation or other purposes shall be considered to be interior finish, shall comply with Section 803 and shall not be considered to be decorative materials or furnishings.” The Chapter 2 definition of interior wall and ceiling finish, in the 2021 Seattle Building Code, Chapter 2, repeats the phrase “acoustical correction.”

That rules out two shortcuts. A panel is not exempt as a thin covering: the 803.2 exemption applies only to materials less than 0.036 in thick applied directly to a wall or ceiling. And it is not judged by the decorative-materials test for curtains and hangings in Section 806.4.

A note on specifications that say “less than 25”

Some specifications tighten the code’s wording. The VA’s section 09 84 33 asks for “Class A, 200 or less smoke density and flame spread less than 25” for the complete composite system. A product with a flame spread index of exactly 25 is Class A under 803.1.2 but fails that sentence, and the VA smoke limit of 200 is lower than the code’s 450. Read the project specification as well as the code.

Which class your room needs

Table 803.13 sets the minimum class by occupancy group, by location (exits, corridors, or rooms) and by whether the building has automatic sprinklers. For rooms in restaurants and offices, the answer is often Class C, while corridors and exit routes ask for more.

The occupancy group comes first. In the 2021 Seattle Building Code, Chapter 3, Group A-2 covers assembly uses “intended for food and/or drink consumption,” including restaurants, cafeterias, taverns and bars. Group B covers office and professional uses. Section 303.1.1 classifies a building or tenant space used for assembly with an occupant load of less than 50 as Group B, so a small cafe may fall under the Group B rules.

GroupExits, sprinkleredCorridors, sprinkleredRooms, sprinkleredExits, not sprinkleredCorridors, not sprinkleredRooms, not sprinklered
A-1 and A-2 (theaters, restaurants, bars)BBCAA (d)B (e)
A-3, A-4, A-5BBCAA (d)C
B, E, M, R-1 (offices, schools, shops, hotels)BC (m)CABC
R-2 (apartments)CCCBBC
R-3 (one- and two-family homes)CCCCCC
Excerpt from IBC 2021 Table 803.13 as published in the 2021 Seattle Building Code, Chapter 8, read November 2026. Footnotes: (d) lobby areas in Groups A-1, A-2 and A-3 not less than Class B; (e) Class C permitted in places of assembly with an occupant load of 300 or less; (m) corridors in ambulatory care facilities Class A or B. Other footnotes and groups omitted; check the edition in force.

Reading the table for common rooms

  • Restaurant dining rooms (A-2). Class C in rooms when sprinklered. Class B when not, but footnote (e) permits Class C in places of assembly with 300 or fewer occupants. Lobbies stay at Class B or better.
  • Offices and meeting rooms (B). Class C in rooms with or without sprinklers. Corridors need Class C sprinklered and Class B without.
  • Homes (R-3). Class C throughout.
  • Exits and corridors in most groups. Stricter, often Class A or B. A panel run that continues from a dining room into an exit passageway takes the stricter class for that stretch.

Rooms, corridors and the partitions between them

Footnote (c) to the table says the requirements for rooms and enclosed spaces “shall be based on spaces enclosed by partitions.” Where a fire-resistance rating is required for structural elements, partitions that do not run from floor to ceiling do not count, and the spaces on both sides are treated as one room or space. In an open restaurant or office where the path to the exit runs through the room, ask the reviewer whether the walls you plan to treat are room walls or corridor walls before you choose a class.

A higher class is always acceptable

The NFPA 5000 first revision text for the 2017 revision cycle states the rule plainly: where Class C is required, Class A or B is permitted, and where Class B is required, Class A is permitted. The IBC table works the same way, since it sets a maximum flame spread. That is one reason a specification may simply require Class A everywhere: it avoids a mistake when a panel line crosses into a corridor.

Example (fictional). The site’s example dining room is a 60-seat room, 40 by 30 ft, with 16 ceiling clouds, 14 fabric wall panels and 4 printed art panels in its plan. It is not a Fibson project. As a restaurant it would be Group A-2. If the building is sprinklered, Table 803.13 asks for Class C in the room. If it is not, the table asks for Class B, and footnote (e) brings it back to Class C as long as the building official confirms an occupant load of 300 or less, which a 1,200 sq ft room with 60 seats is far below. That settles the class for the clouds and any panel with a non-textile face. The fabric wall panels and printed art panels raise a separate question, covered in the next section: if the official treats their faces as textile wall coverings, Class C is no longer the test.

When a fabric face makes a panel a textile wall covering

Section 803.5 gives textile wall coverings their own test routes, and they can demand more than Table 803.13. A textile used as wall finish must be tested in the manner intended for use, with its mounting system and adhesive, and then pass NFPA 286, pass NFPA 265 Method B, or reach Class A under E84 in a sprinklered building.

The 2021 text reads: “Where used as interior wall finish materials, textile wall coverings, including materials having woven or nonwoven, napped, tufted, looped or similar surface and carpet and similar textile materials, shall be tested in the manner intended for use, using the product-mounting system, including adhesive.” The three routes that follow are:

  1. NFPA 286 (803.1.1). The room-corner test for any wall or ceiling finish.
  2. NFPA 265, Method B (803.5.1). The room-corner test written for textile and expanded vinyl wall coverings, run “using the product-mounting system, including adhesive.”
  3. E84 with sprinklers (803.5.2). A Class A flame spread index under ASTM E84 or UL 723, and protection by an automatic sprinkler system installed under section 903.3.1.1 or 903.3.1.2. Specimen preparation and mounting follow ASTM E2404.

Notice what route 3 does. In a sprinklered restaurant dining room, the table alone would accept Class C. A textile wall covering in the same room needs Class A on E84, or a room-corner pass. In a building without sprinklers, route 3 is not available at all.

Which fire evidence fits an acoustic panel under IBC 2021 Chapter 8 Flow diagram. An acoustic panel on a wall or ceiling is interior finish. If its exposed face is not a textile or expanded vinyl covering, ASTM E84 indexes set its class, A, B or C, against Table 803.13, and passing NFPA 286 counts as Class A. If it is a textile on a wall, section 803.5 accepts NFPA 286, NFPA 265 Method B, or E84 Class A plus automatic sprinklers with the specimen prepared to ASTM E2404. If it is a textile on a ceiling, section 803.6 accepts NFPA 286 or E84 Class A plus sprinklers, with no NFPA 265 route. In every route the report must cover the core, face, adhesive and mounting as installed, and the building official decides. Acoustic panel on a wall or ceiling Interior finish under IBC 806.2 Is the exposed face a textile or expanded vinyl wall or ceiling covering? Not a textile covering E84 indexes set the class: A, B or C per Table 803.13; an NFPA 286 pass counts as A Textile on a wall (803.5) NFPA 286, or NFPA 265 Method B, or E84 Class A plus sprinklers (E2404) Textile ceiling (803.6) NFPA 286, or E84 Class A plus sprinklers (E2404); no NFPA 265 route Every route: the report must cover core, face, adhesive and mounting as installed. The local building official decides. No Yes, wall Yes, ceiling
Simplified from IBC 2021 sections 803.1, 803.5 and 803.6 as published in the 2021 Seattle Building Code, read November 2026. Other material sections (foam plastics, HDPE and PP, site-fabricated stretch systems, wood laminates and veneers) have their own rules, and section numbers differ in other editions.

What to ask for under each route

Route Document to request What it must show
NFPA 286 Room-corner test report The complete panel with its mounting system and adhesive; pass against all five criteria
NFPA 265, Method B Room-corner test report The textile as installed on the panel, with mounting system and adhesive
E84 Class A plus sprinklers Tunnel test report and the sprinkler status of the building Flame spread index of 25 or less; specimen prepared to ASTM E2404; a building sprinklered as the section requires

If a supplier offers only a fabric maker’s E84 report, it answers none of these rows on its own, because none of them is about fabric alone.

Ceilings are stricter

Section 803.6 applies the same test-as-intended language to textile ceiling coverings, but allows only NFPA 286 or the E84 Class A plus sprinklers route. There is no NFPA 265 route for ceilings. A committee statement in the NFPA 5000 first revision record makes the same point for that code: “neither textile nor expanded vinyl ceiling coverings are permitted to be tested to NFPA 265.” For fabric-faced clouds, ask early which route the evidence follows.

Site-built stretch fabric systems

The code also defines a site-fabricated stretch system as one “fabricated on site and intended for acoustical, tackable or aesthetic purposes,” made of a frame, a core material, and an outside layer of “textile, fabric or vinyl” stretched taut on the frame. Under section 803.10 such a system must be tested in the manner intended for use and pass NFPA 286 or reach Class A under E84, with specimens prepared to ASTM E2573.

Is a factory-made fabric panel a textile wall covering?

The code text does not say in so many words. A factory-wrapped panel has a woven or nonwoven face, which fits the 803.5 description, but it is also a panel. Different reviewers read it differently. The practical answer is to ask the building official at design stage and to choose evidence that satisfies both readings: a room-corner pass, or Class A for the complete panel plus sprinklers, tested with the real mounting.

Room-corner tests in plain terms

A room-corner test lines part of a small room with the material, lights a burner in the corner and watches whether fire reaches the ceiling, spreads to the edges of the sample or causes flashover. NFPA 286 covers any wall or ceiling finish; NFPA 265 is written for textile and expanded vinyl wall coverings.

The NFPA 265 standard page gives its full title as “Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls,” with 2023 as the current edition. The NFPA 286 standard page gives “Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth,” with 2024 as the current edition. Both list 2027 as the next edition in development.

The acceptance criteria in the IBC

Criterion NFPA 286 (803.1.1.1) NFPA 265 (803.5.1.1)
Flame to the ceiling during the 40 kW exposure Not allowed Not allowed
Flame to the outer edge of the sample Not on any wall or ceiling Not on the 8 by 12 ft walls
Flashover Must not occur Must not occur
Peak heat release rate Not over 800 kW Not listed
Total smoke released Not over 1,000 square meters Not over 1,000 square meters

Why NFPA 286 is the default

The NFPA 5000 first revision statement explains the logic in one sentence: the default test for interior finish is NFPA 286 “because any interior finish material is allowed to be tested to NFPA 286, while not all materials are allowed to be tested to ASTM E84 or to NFPA 265.” The same statement notes that foam plastics, HDPE and polypropylene are not allowed to use E84 in that code. The IBC is similar: HDPE and polypropylene finishes must meet 803.1.1 (section 803.9), and foam plastics may not be used as interior finish except as section 2603.9 allows (section 803.4).

When a room-corner test is worth commissioning

Room-corner tests line the walls, and sometimes the ceiling, of a small test room, so they use far more material than a 24 ft tunnel specimen. Before assuming a project can commission one, ask whether one already exists for the product line. They earn their keep in three cases: a fabric-faced product that will go into buildings without sprinklers, a textile face used on ceilings, and a product line sold across many occupancies where one document should answer every reviewer. If your project falls into one of those cases and the supplier has only E84 data, raise it before design development, not at submittal.

For a specifier, an NFPA 286 pass is the most portable fire document a panel can have. It satisfies the Class A requirement, the textile wall route and the textile ceiling route.

Why a fabric’s Class A and a panel’s Class A are different documents

A fire report describes the specimen that was tested. A fabric tested on one backing, or a core tested bare, says little about the finished panel with its adhesive, edges and frame. Ask what was in the tunnel, and match it to what will be on the wall.

ASTM E84 section 1.4 is the reason. A fabric tested over a noncombustible board can post a low flame spread index because of that support, and the standard says results “do not necessarily relate” to the same material without it. Code sections for specific materials go further by naming the mounting practice: ASTM E2404 for textiles and wall coverings, ASTM E2573 for site-built stretch systems and ASTM E2579 for factory laminates on a wood substrate.

Layers that each need an answer

  • Core. Mineral wool, fiberglass or PET felt, each with its own report. A core report covers the core.
  • Face. The fabric’s report, and for printed faces, the fabric as printed. Inks and coatings change the face. See what to check on printed acoustic panels.
  • Adhesive and frame. Rarely tested on their own, which is why the composite matters.
  • Wood facings. Sections 803.11 and 803.12 give factory laminates on wood and site-applied veneers their own routes. The NFPA 5000 committee noted that veneers applied over a wood substrate show a flame spread “much higher than when applied over gypsum board or over a noncombustible substrate.”
  • Single-material panels. A felt panel with no separate face is simpler, since the report can cover the whole product. Ask whether it was tested at the thickness supplied and whether the lab noted melting or dripping.

How fabric choice interacts with these documents is covered in choosing and cleaning acoustic panel fabric, and how the common cores compare is in PET felt, mineral wool or fiberglass.

Same product, different thickness or color

A report describes one thickness, one density and one face. Suppliers often offer a range of each. Ask for a written statement from the lab or the maker of which variations the report is taken to cover and on what basis, and for a separate report where the variation is large, such as a thicker core, a printed face or a different adhesive. A color change in the same fabric is a smaller question than a change of fabric, but it is still a question worth asking in writing.

Example (fictional). A supplier’s submittal for fabric-wrapped wall panels in a sprinklered office includes three fire documents: an E84 report on the mineral wool core, bare, Class A; an E84 report on the polyester fabric over cement board, Class A; and a letter stating that “the panel is Class A.” None of the three describes the finished panel with its adhesive and resin-hardened edges. The reviewer asks for an E84 report on the complete composite, mounted as it will be installed, or an NFPA 286 report. The supplier is invented for this example.

Common situations and the evidence that fits

The same panel can need different evidence in different rooms. The table below applies the 2021 text to five common situations; each one is hypothetical, and each answer still depends on the official’s reading and the edition in force.

Situation (hypothetical) Class from Table 803.13 Textile route in play? Evidence that fits
Fabric-wrapped wall panels in a sprinklered restaurant dining room (A-2) C Yes, 803.5 for a textile face Complete panel tested as installed: E84 Class A to ASTM E2404, or an NFPA 265 or 286 pass
Fabric-faced panels in the same restaurant’s lobby B or better (footnote d) Yes As above; Class A on E84 satisfies both
Printed art panels in a small cafe with fewer than 50 occupants, no sprinklers (Group B under 303.1.1) C Yes, and the E84 route needs sprinklers NFPA 265 Method B or NFPA 286 on the panel as printed and mounted
Felt clouds over desks in a sprinklered office (B) C Possibly, under 803.6, since felt has a nonwoven surface NFPA 286, or E84 Class A on the felt at the supplied thickness with sprinklers; check 803.15.4 if the felt is 1/4 in or thinner
Fabric panels along an exit access corridor in an office without sprinklers (B) B Yes, and the E84 route needs sprinklers NFPA 265 Method B or NFPA 286 on the complete panel; an E84 Class A report alone does not answer the textile route here

What the table shows

Two patterns stand out. First, the textile route, not the occupancy table, usually sets the bar for fabric-faced panels, and in a sprinklered building that bar is Class A on E84. Second, without sprinklers the E84 route for textiles disappears, and only a room-corner pass will do. The federal UFGS template describes felt panels as “nonwoven polyester felt,” the same word the code uses in its textile sections, which is why felt clouds and baffles deserve the same early conversation as fabric.

If you are planning panels for a small business and the building’s sprinkler status is unknown, find out before you choose finishes. It changes which documents can work.

Why fire-retardant coatings are not a shortcut

Spraying a fire-retardant coating on a panel that failed its test does not create a tested assembly. Model code text says coatings may not be used to obtain compliance for new interior finish, with narrow exceptions for existing surfaces and for factory-coated products tested to an extended tunnel standard.

The NFPA 5000 first revision record for the 2017 revision cycle carries the provision “Fire-retardant coatings shall not be used to obtain compliance with the interior finish requirements of this Code.” Its annex explains the intent: interior finish materials should have their fire performance “determined in their original form.” Coatings are contemplated for renovations and changes of occupancy, where existing surfaces may need treatment under NFPA 703.

Why the annex worries about coatings

The same annex names the practical problem: “Deterioration of coatings applied to interior finishes can occur due to repeated cleaning of the surface or painting over applied coatings.” Panel fabric in a busy restaurant may be cleaned often, which is exactly the condition the annex describes.

The factory-coated exception

The record also permits “factory-applied fire-retardant-coated products that have been listed and labeled to demonstrate compliance with the requirements of ASTM E2768,” the 30-minute extended tunnel test that E84’s own scope points to. In the IBC, section 806.1 adds that fire-retardant coatings in existing buildings “shall be maintained so as to retain the effectiveness of the treatment.” If a supplier proposes a coating, ask which of these provisions it relies on and for the listing.

Code editions and local amendments

Building codes are adopted by states and cities, edition by edition, often with local changes. Section numbers move between editions, and requirements change. Cite the edition in force where the building is, and confirm with the building official.

Numbers move

Compare two Seattle editions. In the 2015 Seattle Building Code, Chapter 8, the E84 classes sat in 803.1.1, the NFPA 286 route in 803.1.2, the NFPA 265 route in 803.1.3, the E84 Class A with sprinklers route in 803.1.4, and the occupancy table was 803.11. In the 2021 edition the same ideas sit in 803.1.2, 803.1.1, 803.5.1, 803.5.2 and Table 803.13. A spec sheet that cites “803.1.3” is citing the NFPA 265 route in one edition and a cross-reference section in the other.

Requirements change

The stretch-system rule shows a real change. In the 2015 Seattle text, site-fabricated stretch systems had to comply with “Section 803.1.1 or 803.1.2,” which then meant any E84 class or an NFPA 286 pass. In the 2021 text they must comply with NFPA 286 “or with the requirements of Class A.” A system that qualified as Class B under the earlier text would not qualify under the later one.

Local amendments are normal

Seattle publishes its code as the IBC with local amendments. Its 2021 definitions chapter states that whenever an International, National or Uniform code is referenced, “it shall mean the Seattle edition of that code, including any local amendments,” and section 201.3 of the same chapter names the Uniform Plumbing Code where the model code names the International one. Other jurisdictions make their own changes. We do not state which edition applies in a given city or state, because that is the building official’s call.

Questions to ask the building official

  1. Which edition of the building code, and which local amendments, apply to this permit?
  2. Is the building fully sprinklered under the section the textile route cites?
  3. What is the occupancy group of each room, and are any treated walls corridor or exit walls?
  4. Will fabric-faced or felt panels be reviewed as textile wall or ceiling coverings?
  5. Will suspended clouds and baffles be reviewed as interior finish or as decorative materials?

Write the answers into the drawings or the specification so the supplier, the installer and the inspector work from the same reading.

We could not read ICC’s online 2024 IBC chapter for this article, so the section numbers here follow the 2021 text. If your jurisdiction has adopted the 2024 edition, check the numbers and wording in that edition before citing them.

Fastening, furring and suspended panels

The fire chapter also cares how panels are held up. Finish must stay attached at high room temperatures, furred panels on rated construction have limits on the space behind them, and thin finishes may not be hung away from rated or noncombustible surfaces unless tested that way.

  • Stability (803.14). Interior finish must be fastened so it “will not readily become detached where subjected to room temperatures of 200°F (93°C) for not less than 30 minutes.” Adhesive-only mounting on panels and clouds deserves a direct question.
  • Furring on rated or noncombustible construction (803.15.1). Finish goes directly against the construction or on furring not over 1-3/4 in deep. The spaces between the furring must be filled with inorganic or noncombustible material, filled with Class A material, or fireblocked at 8 ft or less in every direction.
  • Thin finishes (803.15.4). A finish not over 1/4 in thick must be applied directly to the wall, ceiling or structural element, not furred and not suspended, unless it is noncombustible or reached Class A in tests made with the material furred out or suspended. This can catch thin felt products hung below a noncombustible deck.
  • Decorative hangings (806.2). Curtains, draperies and fabric hangings in Groups A, B, E, I, M and R-1 are limited to 10 percent of the wall or ceiling area they are attached to. Acoustic paneling is interior finish instead, but a loose fabric banner sold as “acoustic” may be treated as a hanging. Ask how a suspended product will be classified.

For submittal language that ties fire evidence to the installed detail, see specifying acoustic panels.

What to put in the submittal, and what to do next

A complete fire submittal for acoustic panels names the code route, the occupancy class required in each location, and a report that covers the complete panel as it will be mounted. Collect these before samples are approved, not after panels are made.

  1. The route. State whether the evidence is offered under 803.1.2 (E84 class), 803.1.1 (NFPA 286), 803.5.1 (NFPA 265 Method B) or 803.5.2 (E84 Class A plus sprinklers), in the edition in force.
  2. The class needed by location. List rooms, corridors and exits separately, with the sprinkler status of the building.
  3. The report. Lab, method and edition, report number and date, both indices or the room-corner results, and a specimen description that lists every layer.
  4. The mounting. How the specimen was mounted or prepared (for example ASTM E2404 for a textile on E84) and whether that matches the installed detail.
  5. Notes from the lab. Any melting, dripping, delamination or support used.
  6. Coatings. None field-applied to reach compliance; any factory coating with its listing.
  7. Fastening. How the panel stays attached at 200°F for 30 minutes, and how any furring cavity is treated on rated construction.
  8. The official’s answer. Whether fabric-faced panels are being treated as textile wall or ceiling coverings.

The acoustic panel spec checklist lists the documents to request from any supplier. Fibson Acoustics designs and makes acoustic panels to order and has not yet tested its finished panels. Its room plans name the core and fabric makers’ reports, state exactly what each report covered, and do not describe a finished panel with a class its reports do not cover, as set out on materials and safety. Architects and designers can request spec sheets and samples through design trade.

Working on a room like this?

Send the size, a few photos and what happens in the space. We reply with questions or an outline of the panel plan.