Good open office acoustics start with absorption on the ceiling, then on walls and columns next to the places people talk most, then on screens between desks. Covering most of the ceiling with absorptive tile, or most of an exposed deck with clouds or baffles, shortens the ring and makes a voice fall away faster with distance, so the room stops building into a roar. It does not stop the person at the next desk from being heard clearly, because that sound travels straight from mouth to ear, and privacy needs screens, distance and often sound masking as well.
This guide is for office managers, workplace designers and tenants planning a fit-out or living with one that echoes. It explains what each kind of absorption changes, how consultants measure open offices, how much ceiling coverage the published guidance asks for, how to treat an exposed deck, and the order to place panels in, with a worked estimate for a fictional exposed-ceiling floor.
What absorption can and cannot change in an open office
Absorption reduces the sound that reaches a listener by reflection; it does not touch the sound that reaches them directly. That one distinction explains most of what panels can and cannot do in an open plan.
The US General Services Administration’s workplace guide calls the toolkit “the ABC’s of noise control: Absorb, Block, Cover” (GSA Sound Matters). Absorb means soft, porous surfaces that soak up sound energy. Block means screens, walls, furniture and distance. Cover means a steady background sound, usually an electronic masking system, that makes distant speech harder to follow. Panels are the A. They help the B work and the C sound comfortable, but they are not a substitute for either.
Three paths from one talker to one listener
Picture a talker at one desk and a listener four desks away.
- The direct path. A straight line from mouth to ear. Nothing overhead changes it. Only a screen, a wall, more distance or turning away does.
- The ceiling path. Sound reflects off the ceiling and lands at desks across the floor. A hard ceiling or an exposed deck sends it far. An absorptive ceiling, or clouds and baffles under a deck, remove most of it.
- The reverberant build-up. Sound bouncing among all the hard surfaces, from every talker at once, forms a general wash. Absorption anywhere in the room lowers it; the ceiling, as the largest free surface, lowers it most.
ISO’s announcement of its open-plan office measurement standard summed up the priorities: “the most important acoustic parameters in open-plan offices are the amount of sound absorption material (usually in the ceiling), the use of screens and background noise” (ISO news, archived).
What a measured office showed
A 2026 conference paper by researchers from KU Leuven, the Technion, the University of Sydney, an acoustics consultancy and Rockfon (a ceiling maker) tested this split in a real 9.6 by 9.45 m office with 14 workstations, 36 hanging ceiling panels covering 57% of the ceiling and six movable partitions (van Dort et al., 2026). Lowering the panels from 3.11 m to 2.10 m cut the reverberation time from 0.69 to 0.59 seconds. But panel height or tilt “had negligible effect” on direct-path speech levels, less than 1 dB, “when no obstruction was present”. Partitions did the privacy work: they raised the speech attenuation between positions to 9 to 13 dB(A), against near zero without them. The authors’ summary is the plainest statement of the rule: “ceiling panels and partitions serve distinct, complementary acoustic functions.”
The paper is a single small room, the authors note the manuscript was not peer reviewed by the conference, and one author works for a ceiling manufacturer. It is a clear demonstration of the mechanism; your office will produce its own numbers.
How open office acoustics are measured
Two families of measurement describe an open office: reverberation time, which describes how long sound lingers anywhere in the room, and the spatial measures of ISO 3382-3, which describe how quickly one voice fades as you walk away from it.
Reverberation time
Reverberation time (RT60) is the time for sound to decay by 60 decibels. It is what Sabine’s formula estimates and what most rating systems cite. LEED v4.1 lists “under 0.8” seconds for an open-plan office without sound masking, at 500, 1,000 and 2,000 Hz (LEED v4.1 BD+C, Table 2). The legacy WELL v1 feature set 0.5 seconds for open offices. Reverberation time is useful for sizing absorption, but on its own it says little about privacy: the large 2025 field study discussed below found that it was not a reliable predictor of how occupants rated their office.
Spatial decay of speech: ISO 3382-3
ISO 3382-3:2022 “specifies a method for the measurement of room acoustic parameters in unoccupied open-plan offices”, using single-number quantities for the condition “when one person is speaking”, which “focus on spatial decay of speech while the quantities in ISO 3382-2 focus on temporal decay of sound” (ISO catalog page, archived). The two that absorption changes most directly are:
- D2,S, the spatial decay rate of speech: how many decibels speech drops each time the distance from the talker doubles. More absorption, especially overhead, makes it larger.
- Lp,A,S,4m, the speech level at 4 meters: how loud a normal voice still is about 13 feet away. More absorption makes it lower.
The standard also defines distances that bring background noise into the picture (comfort distance and distraction distance). Those matter most when deciding between more absorption and sound masking, and the sibling article on sound masking versus acoustic panels explains them in plain terms.
Background sound, the third measure
Background sound from ventilation and equipment is the third of ISO’s “most important” parameters. Owner and federal guidance set a limit on it for open offices: Cornell’s standard allows NC 40 in open-plan offices, and GSA’s open-plan requirements list “Background Noise: NC 40 Maximum”. Panels do little about it. It matters here because a very quiet floor makes every conversation stand out, which is why the same GSA table pairs that limit with a masking level.
Activity-based targets: ISO 22955
ISO 22955:2021, Acoustic quality of open office spaces, sets targets by the kind of work a zone hosts. The van Dort paper summarizes its values for three space types:
| ISO 22955 space type (as summarized by van Dort et al.) | Reverberation time | D2,S | Speech level at 4 m |
|---|---|---|---|
| Type 2: calls with people outside the room (phone and video) | 0.5 s or less | at least 7 dB | 47 dB(A) or less |
| Type 3: collaboration with the nearest workstations | 0.5 s or less | at least 8 dB | 48 dB(A) or less |
| Type 4: low collaboration, individual work | 0.5 s or less | at least 7 dB | 47 dB(A) or less |
The paper’s own measured room did not meet types 2, 3 or 4 in the configurations tested, a reminder of how demanding these targets are, although the authors note their room was smaller than a typical open office.
Start with the ceiling
The ceiling is the first and largest place for absorption in an open office. It is usually the biggest free surface, it is where the long reflection paths between desks bounce, and treating it does not take wall space people want for screens, storage or windows. Every source consulted for this guide gives a ceiling figure; they differ on how good the ceiling must be and how much of it to cover.
| Source | Ceiling guidance for open offices | Who wrote it |
|---|---|---|
| GSA Sound Matters | “Absorption of NRC 0.9 minimum on 100% of ceiling” in open plan workspace | US federal workplace guide, 2011 |
| Acentech, via Propmodo | Any ceiling treatment should have “a Noise Reduction Coefficient rating of at least 0.7”; clouds need “a minimum of 60 to 70 percent area coverage” | Acoustical consultant, quoted in 2022 |
| Cornell 098000 Acoustics | “Specify acoustical ceiling tiles for a 0.75 NRC (minimum of 35 CAC)” | University owner standard, 2019 |
| Rockfon | “Minimum ceiling absorption for achieving acceptable speech privacy is NRC = 0.90” | Ceiling manufacturer, 2019 |
| van Dort et al., citing ISO 22955 | “Full ceiling coverage with a weighted sound absorption coefficient (αw) close to 1 is recommended” | Conference paper, 2026 |
Reading the numbers
NRC (noise reduction coefficient) is the average of a material’s absorption coefficients at 250, 500, 1,000 and 2,000 Hz, and αw is the single-number rating defined in ISO 11654, read from a shifted reference curve. Both describe a material tested on a laboratory floor or in a laboratory mounting, not a room. The guidance clusters at NRC 0.7 to 0.9, with the strictest sources asking for nearly full coverage at the top of that range. A practical reading:
- If your office has a suspended tile ceiling, check the tile’s NRC first. Replacing worn or low-rated tile with high-NRC tile is often the most effective single change, consistent with the field work, cited below, that ranks ceiling absorption first for spatial decay.
- If you must keep a hard ceiling or an exposed deck, aim for treatment that covers most of it, not a scattering.
- CAC, the ceiling attenuation class in Cornell’s line, rates how well a ceiling stops sound passing through the plenum between enclosed rooms. It matters where offices or meeting rooms share a ceiling with the open floor; it is not an absorption rating.
What to ask for before you choose a ceiling product
- The test report, not just the brochure number. An ASTM C423 report from an accredited laboratory, with its edition and date.
- The mounting. ASTM E795 sets how the specimen was mounted for the test, and a tile tested in a suspended-ceiling mounting is not comparable with a board tested flat on the laboratory floor. The report should name it.
- The right single number, stated correctly. NRC is reported to the nearest 0.05 and SAA to the nearest 0.01; ask which one you are being quoted.
- The full frequency table. Speech energy spreads across several bands, and two products with the same NRC can differ at 250 Hz.
- For baffles and other objects, sabins per unit at each frequency, with the spacing used in the test.
- Fire documentation for the assembly as installed, since ceiling products are interior finish.
Why the ceiling helps screens work
Screens and the ceiling depend on each other. Van Dort and colleagues note that, according to ISO 22955, “partition attenuation is substantially higher beneath sound absorptive ceilings, which makes ceiling absorption an essential precondition for maximising partition effectiveness”. Their literature review also cites earlier field work identifying ceiling absorption as “the single most effective parameter for improving spatial decay”. A screen under a hard deck lets sound hop over it by way of the ceiling; under an absorptive ceiling, that hop is gone.
Exposed ceilings: clouds, baffles or panels on the deck
An exposed deck can be treated without hiding it, using suspended clouds, vertical baffles, panels fixed directly to the deck, or a sprayed-on absorptive finish. The choice depends on the look you want, the services overhead and the ceiling height.
Exposed structure is no longer unusual. Acentech’s Ioana Pieleanu told Propmodo in 2022 that “over half of the projects we advise on today don’t have drop ceilings”, and the article notes that sound reflecting off exposed ceilings “can create an echo chamber”. A Construction Specifier article by Sean D. Browne, principal scientist at a large ceiling manufacturer, describes the specific problem in open offices: “reflections off the deck between cubicles in open plan office environments can cause distractions for nearby occupants” (The Construction Specifier).
| Option | How it works | Where it suits | Watch for |
|---|---|---|---|
| Ceiling clouds | Flat panels hung below the deck, absorbing on both faces | Over desk clusters and meeting tables; zones that should feel defined | Coverage must be high to count; coordinate with lights and sprinklers |
| Ceiling baffles | Vertical blades hung in rows, absorbing on both faces | High decks, dense services, long open floors | Rated in sabins per baffle, not NRC; count drives the result |
| Panels fixed to the deck | Absorptive boards attached between joists or to the deck | Keeping the full height and the industrial look | Absorbs on one face only, where suspended elements absorb on both |
| Sprayed-on finish | Absorptive insulation sprayed onto the deck | Decks where nothing may hang below the structure | Appearance and cleaning; confirm fire and emissions documents |
Browne describes clouds as “an interrupted ceiling plane” that “help control both reflections between cubicles and distant reverberation”, and notes that because clouds are discontinuous, “existing building service elements can often be installed in between the clouds”. The Propmodo article mentions sprayed-on thermal and acoustical insulation as one way to “convert an exposed ceiling into one that is sound-absorptive”.
Clouds or baffles
Clouds suit zones: they hang over a team and visually define it. Baffles suit whole floors where the deck is high and crowded with ducts, sprinkler mains and cable trays, because they hang edge-on and leave the services visible and reachable. They are also documented differently. Under ASTM C423, flat products are reported with NRC and SAA, while “the sound absorption of individual objects, such as space absorbers, theater chairs or ceiling baffles will be reported in square meters per unit” (Intertek’s summary of ASTM C423). A baffle schedule is therefore a count times a per-unit value, and comparing a baffle’s NRC with a cloud’s NRC is not a fair test. The sibling article on choosing between ceiling clouds and baffles goes through that comparison in detail, and the baffle layout calculator works out rows and spacing for a given ceiling.
If you lease the space
Tenants often control less of the ceiling than they think. Before planning clouds or baffles under a deck, check the lease and the building rules for who approves attachments to the structure, who must relocate sprinkler heads or detectors if the plan requires it, and whether suspended elements must be removed at the end of the lease. Clouds and baffles hung from cables are usually easier to remove than a sprayed finish or a new tile ceiling, which matters if you expect to move within a few years.
Coordination overhead
Clouds and baffles share the ceiling with sprinkler heads, lights, diffusers, smoke detectors and cable trays. The panel plan has to show each element against those services, and suspended elements that could obstruct sprinkler spray are a question for the fire protection engineer and the local authority, not for the panel supplier. Wherever a cloud or baffle hangs over a walkway, keep at least 80 inches of clear height below it, the vertical clearance the 2010 ADA Standards require in 307.4.
How much coverage is enough
Two rules of thumb circulate, and both are worth testing with arithmetic before you rely on them.
- Pieleanu’s 60 to 70 percent. “Adding just one cloud here and there isn’t sufficient,” she said; clouds need 60 to 70 percent area coverage “to provide significant sound absorption.”
- Browne’s one baffle per 40 square feet. He writes that “one fiberglass baffle per 4 m2 (40 sf), or 20 percent coverage, reduces reverberation time on average by approximately 50 percent.”
Sabine’s formula (RT60 = 0.049 × V ÷ A in feet) shows why a percentage cut depends on the room. Halving reverberation time means doubling the room’s total absorption. In a bare concrete shell, a modest number of baffles can double it. In a carpeted, furnished office that already has a fair amount of absorption, the same baffles add a smaller share and cut the time by less. The worked example below shows the effect in a carpeted office.
Worked example: an exposed-deck office floor
The estimate below compares clouds, baffles and a mixed plan for one invented floor. Coefficients and per-baffle values are planning assumptions, not test results.
Example (fictional). Not a Fibson project. An open office floor 60 by 40 ft with 14 ft to an exposed concrete deck, carpet tile, 800 sq ft of window glass and 24 workstations. Volume 60 × 40 × 14 = 33,600 cu ft, so 0.049 × V = 1,646.4.
| Surface | Area (sq ft) | Coefficient | Sabins |
|---|---|---|---|
| Floor, carpet tile | 2,400 | 0.25 | 600.0 |
| Deck, exposed concrete | 2,400 | 0.02 | 48.0 |
| Window glass | 800 | 0.05 | 40.0 |
| Walls, painted drywall | 2,000 | 0.05 | 100.0 |
| Desks, chairs, screens and storage (allowance) | 100.0 | ||
| Total | 888.0 |
RT60 = 1,646.4 ÷ 888.0 = 1.85 seconds. For a planning target of 0.8 seconds (the LEED v4.1 open-plan figure without masking) the floor needs 1,646.4 ÷ 0.8 = 2,058 sabins, about 1,170 more.
- Baffles at Browne’s density. One per 40 sq ft is 60 baffles. At an assumed 10 sabins each, that adds 600 sabins: 1,646.4 ÷ 1,488.0 = 1.11 seconds, a 40% cut, not 50%, because the carpet already supplied much of the absorption.
- Baffles at twice the density. 120 baffles add 1,200 sabins: 1,646.4 ÷ 2,088.0 = 0.79 seconds.
- Clouds at Pieleanu’s coverage. Forty-eight 4 by 8 ft clouds (1,536 sq ft, 64% of the floor area) at an assumed 0.90 add 1,382.4 sabins: 1,646.4 ÷ 2,270.4 = 0.73 seconds.
- Mixed plan. Thirty-six clouds over the desk clusters (1,152 sq ft, 48%) add 1,036.8 sabins; 24 baffles over the kitchen and the main walkway add 240; sixteen 2 by 4 ft wall panels by the collaboration area and on the solid wall opposite the windows (128 sq ft at an assumed 0.80 replacing drywall at 0.05, net 0.75) add 96.0. Total added 1,372.8; 1,646.4 ÷ 2,260.8 = 0.73 seconds.
Reaching the stricter 0.5 second figure would need 1,646.4 ÷ 0.5 = 3,292.8 sabins, nearly four times the starting absorption, which shows how hard the stricter figure is to reach on a tall floor without a continuous absorptive ceiling.
What the example shows
- A rule of thumb stated as a percentage depends on the starting room. Browne’s density cut this carpeted floor’s time by 40%. In a bare shell with a concrete floor, the same 60 baffles would be a much larger share of the total and the cut would be bigger.
- Pieleanu’s coverage figure and the LEED target agree here. Clouds over about two thirds of the floor reach 0.73 seconds. Clouds over a quarter of it would not come close.
- In this example, the mixed plan costs no performance. Putting clouds where people sit and baffles where services are densest reaches the same estimate as clouds everywhere, and keeps the walkway and kitchen ceilings accessible.
- The floor finish changes the ceiling’s job. Swap the carpet tile for polished concrete at an assumed 0.02 and the floor supplies 48 sabins instead of 600. Reaching 0.8 seconds would then need about 1,722 added sabins, or roughly 1,913 sq ft of clouds at 0.90: 80% of the floor area.
- Volume sets the floor. A 14 ft deck makes the stricter targets expensive. Hanging clouds lower helps: in van Dort’s measurements, lowering the panels shortened the reverberation time, which the authors attribute to the smaller effective volume beneath them.
Walls, columns and glass: the second layer
After the ceiling, put absorption on walls and columns next to the places where people talk most and next to large hard surfaces. Wall panels at seated head height catch voices at the height they travel and break up reflections between parallel walls.
Where wall panels earn their place
- Beside collaboration areas and team tables, where several people talk at once and their voices would otherwise reflect back over the desks.
- Near call-heavy teams, such as sales or support, on the walls and columns closest to them.
- Kitchens, coffee points and reception, which can be among the loudest parts of the floor and deserve their own treatment zone.
- The solid wall opposite a window wall, so that glass and drywall do not face each other bare.
- Columns in the middle of the floor, wrapped or faced with panels, which add absorption where there is no wall at all.
GSA’s guidance for open plan workspace pairs its ceiling figure with “absorption of NRC 0.8 minimum on 25% of walls”, and for open workspaces generally suggests “sound absorbing materials on ceiling and all available wall surfaces including windows (e.g., curtains or sound-absorbing shades)”. Fabric-wrapped, felt and printed panels all serve here; the choice is about appearance, durability and the test report behind each.
Absorption in furniture
Furniture adds absorption close to the talkers, where it intercepts sound early. GSA’s guide describes low workstation partitions with “acoustic absorption of NRC 0.7 in partition material located in front of the worker when seated”. The Propmodo article reports that acoustical consultants “recommend placing sound-absorptive furniture like this”, meaning upholstered chairs and sofas, “near the office’s most common noise sources”. A soft-seating area beside the kitchen, or fabric-faced storage along a call-heavy team, does acoustic work that a bare credenza does not.
Keep walkways safe
Wall panels along corridors and walkways must respect the protruding-objects rule. Under the 2010 ADA Standards, objects with leading edges more than 27 inches and not more than 80 inches above the floor “shall protrude 4 inches (100 mm) maximum horizontally into the circulation path” (307.2). A panel whose depth with its mounting is under 4 inches meets it; deep panels and panels on standoffs should be checked against their actual depth, especially next to doors and in narrow corridors.
Screens, layout and distance: where absorption needs help
Speech privacy between desks comes mainly from blocking the direct path and from distance, with absorption overhead as the precondition that lets those measures work. This is where panels stop and furniture, layout and sometimes masking take over.
What screens do, and what they need
Van Dort and colleagues measured partitions 2.1 m (about 83 inches) tall. With them in place, the spatial decay rate rose by about 2 to 3 dB, the speech level at 4 m fell by 2 to 6 dB(A), and speech attenuation between positions reached 9 to 13 dB(A). Pushing partitions flush against a wall added another 0.5 to 3 dB(A) “by blocking first-order reflections”, and partitions near the talker helped more than partitions near the listener. Citing ISO 22955, the authors recommend screens taller than 1.5 m (about 59 inches) to maximize attenuation between workstations.
GSA strikes a note of caution about ordinary cubicle walls: its guide says higher cubicle partitions “block standing line of sight but provide small amounts of additional acoustical shielding”, and that the visual privacy “may encourage people to talk louder”. The two views fit together. Tall screens placed near talkers under an absorptive ceiling measurably reduce speech transfer; moderately taller cubicle walls under a hard ceiling mostly change what people can see.
Calls at the desk
Phone and video calls are the hardest case. ISO 22955 gives zones where people talk to callers outside the room their own targets (space type 2 in the table above), and GSA lists “employees on the phone (especially standing above the acoustic absorption of the workstation or on a speakerphone)” among the main distractions on an open floor. Absorption overhead keeps a call from carrying across the room by way of the ceiling, but the people at the next desks still hear it directly. Floors with many calls usually need a call zone with tall screens and heavy treatment, enclosed rooms or booths, or both, in addition to the ceiling.
Distance and grouping
GSA notes that “people are now six to eight feet apart at their desks and up to twelve feet on center would be required to realize any appreciable reduction in distraction”. ISO’s guidance on its open-plan standard suggests a layout rule that costs nothing: “bring together people who want to share information, preferably within the distraction distance, and to keep further away those belonging to other groups.” Put teams that talk to each other together, put quiet work at the far end of the floor, and keep the kitchen and the call-heavy team away from both.
When the complaint is privacy
If people say they can follow every word of the conversation two desks away, more panels will not fix it. Absorption removes the reverberant wash around a voice; with the wash gone, a nearby voice can even seem a little clearer. The usual answer is the C in GSA’s ABC: a controlled background sound. The sibling article on sound masking versus acoustic panels sets out when an office needs it, at what level, and when only an enclosed room will do.
A placement order for an open office
Follow the order below, and stop at each step to check whether the remaining complaints are about ring and loudness (more absorption helps) or about overheard words (blocking, layout or masking helps).
- Walk the floor at a busy hour. Note where the noise comes from and where complaints come from. The open office acoustics checklist lists what to record.
- Rate the ceiling. Suspended tile: find its NRC. Hard ceiling or exposed deck: measure its height and map the services.
- Treat the ceiling to a high standard. High-NRC tile, or clouds and baffles over most of the floor, coordinated with lights, sprinklers and diffusers.
- Treat the noisy zones. Kitchen, reception, collaboration tables and call-heavy teams get wall and column panels at seated head height.
- Break hard parallel pairs. Window wall versus solid wall, glass meeting-room fronts versus the wall opposite.
- Add or move screens. Tall enough, close to the talkers, flush to walls where possible.
- Rearrange teams. Group people who share information; separate quiet work from talkers.
- Decide on masking. If the remaining complaint is intelligible speech, plan masking with a consultant or supplier, after the absorption is in place.
| Zone | First treatment | Second treatment | What it will not fix |
|---|---|---|---|
| Desk clusters | Clouds or high-NRC tile overhead | Tall screens near talkers | Neighbors heard directly across a low screen |
| Collaboration tables | Clouds over the table | Wall panels beside it | Talk carrying to quiet zones without distance |
| Kitchen and coffee point | Baffles or clouds | Wall panels on the nearest walls | Machine noise at the source |
| Reception | Ceiling treatment | Wall or printed panels behind the desk | Visitors’ conversations reaching nearby desks |
| Walkways | Baffles, keeping 80 inches clear | Wall panels within the 4 inch limit | Footfall on hard floors |
| Glass meeting-room fronts | Treatment inside the room | Wall panels on the open-floor side opposite | Speech leaking out of the room |
What to expect, and how to check the result
Expect a room that rings less, builds up less as it fills, and lets voices fall away faster across the floor. Do not expect privacy at the next desk from panels alone. Measure before and after so you can tell which change did what.
Recent field evidence on what occupants notice comes from a 2025 study in The Journal of the Acoustical Society of America, which measured 28 open-plan offices in nine Australian buildings and surveyed 349 occupants (Yadav et al., 2025). Increased absorption, seen as lower speech levels at 4 m and shorter comfort distances, “reduced dissatisfaction with noise disturbance in general, which is as expected”. The authors add a caution that matches this guide: “even exorbitant sound absorption alone is unlikely to be beneficial against noise from nearby sources.” They also found that reverberation time measured in the empty offices was not a reliable predictor of occupant ratings, which is a good reason to judge results by more than one number. The sibling article on what research says about open-office noise and work puts that study alongside the wider evidence.
How to check
- Reverberation time. Measure before and after at several points on the floor, or have a consultant measure to ISO 3382-2. Compare with your estimate.
- Spatial decay. For a large fit-out, ask a consultant to measure D2,S and the speech level at 4 m along a line of desks to ISO 3382-3, before and after.
- Occupants. Ask the same short questions before and after: how often noise disturbs concentration, how often people overhear conversations, and whether they feel their own calls are overheard. Yadav and colleagues used an adapted form of the questionnaire in ISO 22955 Annex D, which is a reasonable model.
Next steps for your floor
Start with the floor you have, not with a product. Record the ceiling, the floor finish, the glass and the places people talk, run the estimate, and decide how much of the problem is ring and how much is privacy.
- Record ceiling type, height, NRC if known, and the services overhead.
- Mark the noisy zones and the quiet zones on a floor plan.
- Estimate reverberation time now and after treatment, using the same Sabine steps as the example.
- Choose a ceiling strategy: high-NRC tile, clouds over most of the desks, baffles where services are dense, or a mix.
- List wall and column locations for panels at seated head height, checked against the 4 inch walkway limit.
- Note where screens, layout changes or masking are needed for privacy.
- Ask every supplier for ASTM C423 reports with the mounting type, per-unit values for baffles, and fire documentation for the assembly as installed.
Fibson designs and makes acoustic panels to order, including ceiling clouds, baffles and wall panels, and plans each room before anything is ordered. Its offices page describes what an office plan covers. If you would like a written estimate for your floor, send the floor plan and photos of the ceiling.