WELL's sound requirements, and where acoustic panels fit

The WELL sound concept for specifiers: v2 S04 reverberation limits, S05 NRC coverage tiers, what changed since v1, and the panel data to collect.

A felt bento box seen from above with nine compartments, two filled with soft olive and saffron felt rolls and the rest holding small pieces or left empty.
Reader question
What does the WELL Building Standard require for reverberation and sound-absorbing surfaces, and how do acoustic panels help a project meet it?

In the current version of WELL v2, labeled Q2 2025 when we checked in November 2026, two features decide what acoustic finishes must do. S04 Reverberation Time caps reverberation by room type and volume, for example 0.6 seconds or less in conferencing and learning areas under 10,000 cubic feet, and can be shown either by modeling or by on-site testing. S05 Sound Reducing Surfaces sets minimum NRC or alpha-w values over a share of the ceiling and walls, such as 0.75 on at least 75% of the available ceiling in open workspaces. Acoustic panels help with both: they supply the absorption a reverberation model or test needs, and they can be the qualifying surfaces themselves, provided the supplier documents tested ratings and areas.

The numbers most people find first, 0.6 seconds for conference rooms and 0.5 seconds for open offices, come from WELL v1, which its publisher now marks as a legacy version. This article maps the current Sound concept as it touches finishes, compares it with the versions that still rank in search results, and lists the documents a panel supplier should hand a WELL team. General reverberation targets outside WELL are covered in what reverberation time your room should have.

How the WELL v2 Sound concept is organized

WELL v2 groups its acoustic features in the Sound concept, numbered S01 to S09. One is a precondition that every project must meet; the rest are optimizations that earn points. Only two of them are about absorptive finishes, but a panel plan touches three or four.

The International WELL Building Institute (IWBI) publishes the standard through a web application, and the current text is served to that application as structured data. The feature list below comes from that data for the version labeled “WELL v2, Q2 2025,” read on November 22, 2026.

Feature Type Maximum points What it covers Do panels play a part?
S01 Sound Mapping Precondition None Acoustic zones on the plans and an acoustic design plan Yes, as part of the plan
S02 Maximum Noise Levels Optimization 3 Background noise from HVAC, outside and building services No; absorption does not lower HVAC noise
S03 Sound Barriers Optimization 3 Sound isolation of walls and doors (STC, NIC) No; panels do not block sound between rooms
S04 Reverberation Time Optimization 2 Reverberation limits by room type and volume Yes, directly
S05 Sound Reducing Surfaces Optimization 2 Minimum NRC or alpha-w over a share of ceilings and walls Yes, directly
S06 Minimum Background Sound Optimization 2 Sound masking, plus a bonus part tied to S03 or S05 Indirectly, through S05
S07 Impact Noise Management (beta) Optimization 3 Footfall and impact noise No
S08 Enhanced Audio Devices Optimization 2 Audio devices No
S09 Hearing Health Conservation (beta) Optimization 1 Hearing health No

Two of the “no” rows deserve a sentence each. Background noise in S02 is set by mechanical systems and the building envelope, so absorption barely changes it. Sound isolation in S03 is a property of walls, doors and the paths around them; NRC vs STC explains why panels inside a room do not stop sound passing through its walls.

S01 matters more than its zero points suggest. Its first part asks for a floor plan that labels loud, quiet, mixed, circulation and not-applicable zones, plus a plan for mitigating sound between loud zones that border quiet ones. Its second part asks for an acoustic design plan, either from the project team or from “a professional in acoustics,” covering “background noise, speech privacy, reverberation time and/or impact noise.” A room-by-room panel plan with reverberation estimates is a natural piece of that document.

Which WELL version you are working to

Three generations of WELL acoustic text circulate, and their numbers differ. Before anyone quotes a target, confirm which version the project is registered under.

TopicWELL v1 (legacy)WELL v2 pilot (Q4 2022)WELL v2 (Q2 2025)
Where reverberation sitsFeature 78 Reverberation timeS04 Sound Absorption, Part 1S04 Reverberation Time
Conference rooms0.6 s maximum0.6 s or less0.6 s or less under 10,000 cu ft; 0.8 s to 20,000 cu ft; 1.0 s above
Open offices0.5 s maximumNo reverberation limit listedNo reverberation limit listed; handled through S05 surfaces
How it is shownPerformance testNot stated in the data we readDesign (modeling report) or performance (on-site test)
Where absorptive finishes sitFeature 80 Sound reducing surfacesS04 Parts 2 and 3S05 Sound Reducing Surfaces
Open office ceilingNRC 0.9 or more on the entire ceilingNRC or alpha-w 0.7 on at least 75%0.75 on at least 75% (Tier 1) or 0.90 on all (Tier 2)
Conference room ceilingNRC 0.8 or more on at least 50%0.7 on at least 50%0.75 on at least 50% (Tier 1) or 0.90 on all (Tier 2)
Conference room wallsNRC 0.8 on at least 25% of surrounding walls0.7 on 25% of at least two walls0.75 on 25% of one wall (Tier 1) or 0.80 on 25% of two perpendicular walls (Tier 2)
Sources: WELL v1 Features 78 and 80 (standard.wellcertified.com, marked legacy); WELL v2 pilot Feature S04 and WELL v2 Features S04 and S05 as served by IWBI's WELL v2 API (v2-api.wellcertified.com), all checked November 2026. Thresholds are as published for each version; confirm the version your project is registered under.

The v1 pages are the ones search engines still return. WELL v1 Feature 78 lists maximum RT60 values of 0.6 seconds for conference rooms and 0.5 seconds for open offices, verified by a performance test. Feature 80 asks open office ceilings for an NRC of at least 0.9 “for the entire surface area of the ceiling (excluding lights, skylights, diffusers and grilles),” and conference rooms for 0.8 on at least half the ceiling.

The v2 pilot, whose last English version in IWBI’s data is labeled Q4 2022, folded all of this into one feature, S04 Sound Absorption. It had three parts worth a point each: reverberation limits by room type, ceiling coverage at NRC or alpha-w 0.7, and wall coverage at 0.7.

WELL v2 split that feature in two. IWBI’s own summary of changes from the pilot, read here through a Wayback Machine capture because the support site blocks automated requests, says that S04 Reverberation Time “includes two pathways for projects to achieve the feature, including a design-based option and a performance-based option,” and that S05 Sound Reducing Surfaces draws on the pilot’s S04 Sound Absorption.

Feature names are the quickest way to tell which version a document is quoting. A two- or three-digit feature number, such as 78 Reverberation time or 80 Sound reducing surfaces, is WELL v1. “S04 Sound Absorption” with parts for reverberation, ceilings and walls is the v2 pilot. “S04 Reverberation Time” next to “S05 Sound Reducing Surfaces” is WELL v2. Not every design guide, brochure or owner standard says which version it was written against, so check the names before trusting the numbers.

The practical consequence: a specification copied from a v1-era design guide will ask for the wrong numbers. Owner standards written before v2 can carry them too, as the Cornell example later in this article shows.

S04 Reverberation Time: the limits and the two pathways

S04 has one part, “Achieve Reverberation Time Thresholds,” worth 2 points (1 point under WELL Core). It applies “for projects in which the room types listed in the table cumulatively make up at least 10% of occupiable project area,” and it excludes dwelling units and guest rooms.

The current S04 table is the same for both pathways:

Room type Room volume Reverberation time
Areas for learning, lectures and conferencing Under 10,000 cu ft (280 cubic meters) 0.6 s or less
Areas for learning, lectures and conferencing 10,000 to 20,000 cu ft (280 to 570 cubic meters) 0.8 s or less
Areas for learning, lectures and conferencing Over 20,000 cu ft (570 cubic meters) 1.0 s or less
Areas with regularly used PA systems Any 1.5 s or less
Areas for dining Any 1.0 s or less
Areas for fitness Under 10,000 cu ft 0.8 s or less
Areas for fitness 10,000 to 20,000 cu ft 1.1 s or less
Areas for fitness Over 20,000 cu ft 1.8 s or less
Areas for music rehearsal Under 10,000 cu ft 1.1 s or less
Areas for music rehearsal 10,000 to 20,000 cu ft 1.4 s or less

A note in the feature handles mixed rooms: “Where room types include multiple use types (e.g., learning and fitness) use the limits that include the lower reverberation time or range.” A training room that doubles as a yoga studio takes the learning limit.

Two absences are worth noticing. Open workspaces have no row, so in v2 an open office is not held to a reverberation number at all; its acoustic finishes are judged through S05 instead. Enclosed private offices have no row either.

IWBI’s own rationale for the feature explains what it is protecting. The S04 text says that spaces with high reverberation “may have increased ambient noise levels and reduce speech intelligibility,” and that studies have linked high reverberation in classrooms to greater auditory workload and to reduced cognition, memory retention and concentration. Its evidence note names the remedy in one line: “Reverberation time can be controlled by adding absorptive surface finishes at ceilings, walls and furniture.”

Design pathway or performance pathway

The two options carry the same table but different evidence:

  • Reverberation time, design. Verified with a modeling report, submitted as an audited technical document. This is a calculated prediction from room volumes and finishes.
  • Reverberation time, performance. Verified by a performance test, plus “a list of room volumes for all applicable spaces.” The feature points to IWBI’s Performance Verification Guidebook for “sensor/testing requirements, required testing duration and compliance calculations.” We did not read that guidebook for this article, so its procedural details are not summarized here.

The design pathway suits new construction, where finishes are still being chosen. The performance pathway suits existing buildings and projects that would rather measure than model, and it rewards treatment that was actually installed rather than drawn.

Showing compliance on the design pathway

A modeling report for S04 is, at its simplest, a reverberation estimate for every applicable room, with its inputs shown. Sabine’s formula is the usual starting point: in feet, RT60 = 0.049 × V ÷ A, where V is the room volume and A the total absorption in sabins (square feet of perfect absorption). HyperPhysics gives the constant as 0.049 seconds per foot, or 0.16 per meter in metric.

The inputs are what a reviewer will check. List each surface’s area, the absorption coefficient used and where that coefficient came from, the volume, and any allowance for furniture. A panel’s contribution is its area times its tested coefficient, minus the coefficient of the surface it covers.

Example (fictional). A conference room measures 20 by 16 ft with a 9 ft ceiling, so its volume is 2,880 cu ft, under the 10,000 cu ft line, and its S04 limit is 0.6 seconds. The top line of the formula is 0.049 × 2,880 = 141.1.

All coefficients below are planning assumptions for the example, not test results. Floor, carpet tile, 320 sq ft × 0.30 = 96.0 sabins. Ceiling, painted gypsum board, 320 × 0.05 = 16.0. One long wall is glass, 180 sq ft × 0.12 = 21.6. The other walls are painted gypsum board, 468 sq ft × 0.05 = 23.4. Table and chairs, an allowance of 20.0. Total 177.0 sabins, so RT60 = 141.1 ÷ 177.0 = 0.80 s, over the limit.

To reach 0.6 s the room needs 141.1 ÷ 0.6 = 235.2 sabins, 58.2 more than it has. The plan treats 144 sq ft of ceiling, half of an assumed 288 sq ft of available ceiling, with panels at a planning coefficient of 0.80 in place of gypsum at 0.05: 144 × 0.75 = 108.0 sabins. The total becomes 285.0 and RT60 = 141.1 ÷ 285.0 = 0.50 s.

Adding 40 sq ft of wall panels at the same planning coefficient on the 16 ft end wall, which is 144 sq ft, covers 28% of that wall and adds 40 × 0.75 = 30.0 sabins. The total becomes 315.0 and RT60 = 141.1 ÷ 315.0 = 0.45 s.

Estimated reverberation time of the fictional conference room against the S04 limitHorizontal bars of Sabine estimates for a fictional 20 by 16 foot conference room. As built: 0.80 seconds. With half the available ceiling treated: 0.50 seconds. With ceiling treatment plus wall panels on 28 percent of one end wall: 0.45 seconds. A dashed line marks the 0.6 second S04 limit for conferencing areas under 10,000 cubic feet; the first bar crosses it and the other two stop short of it. As built Half of ceiling treated Ceiling plus one wall 0.80 s 0.50 s 0.45 s S04 limit, 0.6 s 0 0.25 0.50 0.75 1.00 Estimated RT60 (seconds), Sabine
Fictional example data for illustration: Sabine estimates for the invented conference room above, using planning-assumption coefficients, not test results. Limit from WELL v2 (Q2 2025) Feature S04, checked November 2026.

The example also previews S05. Half the available ceiling at 0.75 or better is S05’s Tier 1 ceiling requirement for conferencing areas, and 25% of one wall at 0.75 is its Tier 1 wall requirement. The same panels can serve both features, as long as the tested rating, not the planning coefficient, clears 0.75.

Three cautions keep a model honest. First, run it at the frequencies the reviewer expects; the S04 table itself does not name bands in the text we read, so state the bands you used. Second, Sabine assumes sound spreads evenly, which is less true in long, narrow rooms or rooms with all their absorption on one surface. Third, keep the inputs traceable: a coefficient without a named test report is an assumption, and the report should say so. The reverberation time calculator runs the same arithmetic for a single band, with Sabine and Eyring side by side.

The performance pathway: what testing involves

On the performance pathway, a WELL Performance Testing Agent measures the finished rooms. The Sound concept’s general testing notes, served with the feature data, set the ground rules that apply across its tests.

  • Equipment. A “Type 1/Class A sound level meter with whole and ⅓-octave measuring capabilities,” calibrated annually, with a bandwidth of at least 31.5 Hz to 8 kHz.
  • Positions. Measurements at least 1.2 m (4 ft) above the floor, and not within 1.5 m (5 ft) of noise sources, windows or other exterior penetrations.
  • Conditions. Avoid transient sounds such as talking or doors closing, and test “when the space is unoccupied or when the fewest number of people are on-site or nearby.”
  • Safety. The notes say it is “highly recommended” that the agent use hearing protection when operating loudspeakers, a reminder that reverberation tests use loud test signals.

The notes also say that rotating the meter at arm’s length, a technique used for some level measurements, “does not apply to Reverberation Time (RT60) tests.” For the method itself, the feature defers to the Performance Verification Guidebook. Owner standards such as Cornell’s point to ISO 3382-2, the international method for measuring reverberation time in ordinary rooms.

Teams on this pathway can lower the risk of a failed test with a check of their own before the agent arrives. A phone reading is not a compliance test, but it can flag a room that is far off; how to measure reverberation time with a phone explains how to take one and how far to trust it.

S05 Sound Reducing Surfaces: coverage tiers by room type

S05 is where acoustic panels are named most directly. Its single part, “Implement Sound Reducing Surfaces,” uses the same 10% applicability rule as S04, excludes dwelling units, is verified with a design specification, and pays 1 point for Tier 1 or 2 points for Tier 2 (0.5 and 1 point under WELL Core).

The S05 table reads:

Room type What is measured Tier 1 Tier 2
Open workspaces Minimum NRC or alpha-w on the ceiling 0.75 for at least 75% of available ceiling area 0.90 for all available ceiling area
Open workspaces Furniture height and NRC or alpha-w Not required Partial height barriers at least 4 ft (1.2 m) high, NRC or alpha-w 0.70, between all opposing workstations
Areas for conferencing and learning Ceiling 0.75 for at least 50% of available ceiling area 0.90 for all available ceiling area
Areas for conferencing and learning Walls 0.75 on at least 25% of one wall 0.80 on at least 25% of two perpendicular walls
Areas for dining Ceiling 0.75 on at least 50% of available ceiling area 0.90 for all available ceiling area

Three details shape how panels are chosen. The metric is NRC or alpha-w, so a product tested in the US to ASTM C423 and one tested in Europe to ISO 354 with an ISO 11654 rating can both qualify; the report must state which. The values are minimums for the area counted, so a takeoff should count only surfaces whose own rating meets the threshold. And coverage is measured against “available ceiling area,” a term the project team should confirm in the standard’s glossary before it builds a takeoff.

The Tier 2 open-workspace row is the only place S05 reaches into furniture. Desk screens at least 4 ft high with a rating of 0.70 between opposing workstations count, so a furniture dealer’s acoustic test report becomes a WELL document too.

Why S05 starts with the ceiling

The S05 evidence note gives the reasoning behind the table’s emphasis: “Ceilings typically provide the greatest area of coverage where highly absorptive materials can offer the best performance in reducing reverberation and controlling speech intelligibility and occupied noise levels.” It adds: “Wall treatment can reduce reflections that impact performance of speech intelligibility with teleconferencing equipment.” That lines up with the table, where conferencing and learning areas carry a wall requirement and open workspaces do not.

NRC or alpha-w: one panel can pass one and fail the other

S05 accepts “NRC OR Alpha-w,” and the two ratings for one product can differ by more than the gap between the tiers. NRC is the average of the coefficients at 250, 500, 1,000 and 2,000 Hz, rounded to 0.05, as Intertek’s summary of ASTM C423 puts it. Alpha-w comes from ISO 11654, which fits a reference curve to the octave-band coefficients instead of averaging them.

A 2025 lab report by SRL Technical Services for Rockwool UK shows the effect on one material, a 25 mm (about 1 in) mineral wool slab tested to ISO 354 in Type A mounting. The lab reported both ratings for each specimen:

Specimen NRC (calculated to ASTM C423) Alpha-w (ISO 11654) Tier 1 threshold of 0.75
RW3 slab, 25 mm 0.70 0.55 (MH) Fails on both
RW5 slab, 25 mm 0.75 0.60 (MH) Passes on NRC, fails on alpha-w
RWA45 slab, 25 mm 0.65 0.55 (H) Fails on both
RW3 slab, 100 mm 1.15 1.00 Passes on both

The letters after the alpha-w values are ISO 11654 shape indicators; the report explains that they “show the frequencies at which the practical sound absorption coefficient exceeds the shifted reference curve by 0.25 or more.” In these tests the thin slabs, which absorb well in the upper bands and poorly in the lower ones, scored higher on NRC than on alpha-w. Because S05 accepts either, a supplier may quote the more favorable one; the specification should say which rating it relies on, and the report should contain it. The report itself is a good model of what to ask for: both ratings, the full band table and the mounting.

S06 rewards S05 at Tier 2

S06 Minimum Background Sound is mostly about sound masking, which sound masking or acoustic panels covers in depth. Its second part, “Provide Enhanced Speech Reduction,” is earned by achieving the masking part and two points in either S03 Part 2 or S05 Part 1. In other words, a project with masking that reaches Tier 2 in S05 picks up an extra S06 point.

Where acoustic panels fit in S04 and S05

Each panel type maps onto the features differently. The table below is a planning aid, not a WELL interpretation; where the standard’s wording leaves room, confirm with the project’s WELL coach or IWBI before counting.

Panel type S04 (reverberation) S05 (surfaces) Question to settle
Ceiling clouds Adds absorption to the model or the test Counts if the ceiling coverage can include suspended units How “available ceiling area” treats clouds hung below a hard ceiling
Ceiling baffles Adds absorption, often rated in sabins per baffle Often tested as objects, without an NRC Whether a per-unit rating can satisfy an NRC or alpha-w threshold
Direct-applied ceiling panels Adds absorption Counts toward ceiling coverage Rating in the mounting used, usually Type A
Fabric-wrapped wall panels Adds absorption Counts toward wall coverage in conferencing and learning areas Wall area basis: 25% of the whole wall or of a net area
Printed art and felt panels Adds absorption Counts if the printed or felt product has its own tested rating Whether the test covered the print or face actually used
Desk screens Small effect on room reverberation Tier 2 open workspaces, 4 ft and 0.70 Height measured from the finished floor

The two ceiling questions matter most in offices with exposed structure, where clouds and baffles are often the only practical ceiling treatment. How to compare the two fairly is the subject of clouds vs baffles, and where they go in an open office is covered in open office acoustics.

Panels also have limits under WELL that are worth stating plainly. They do not contribute to S02’s background noise limits or S03’s sound isolation. A meeting room that meets S04 and S05 can still leak speech into the corridor; that is a wall and door problem.

Example (fictional). An open office floor has 6,000 sq ft of ceiling, of which the team’s takeoff counts 5,400 sq ft as available after lights and diffusers. Tier 1 of S05 needs a product rated 0.75 or better over at least 75% of that area, 0.75 × 5,400 = 4,050 sq ft. Tier 2 needs 0.90 over all 5,400 sq ft, plus desk screens at least 4 ft high rated 0.70 between every pair of opposing workstations. The gap between the tiers is 1,350 sq ft of ceiling, a higher rating everywhere and the screens.

Dining areas: one room checked against S04 and S05

WELL projects with staff cafes and dining rooms meet the dining rows of both features: 1.0 second or less in S04, whatever the volume, and in S05 a ceiling rated 0.75 or better on at least half the available area for Tier 1. Meeting the first does not mean meeting the second, as the site’s fictional example room shows.

Example (fictional). The example room is a 60-seat dining room, 40 by 30 ft with an 11 ft ceiling, so its volume is 13,200 cu ft and 0.049 × 13,200 = 646.8. It is not a Fibson project, and its coefficients are planning assumptions, not test results. As built, unoccupied and furnished, it holds 276.4 sabins at mid frequencies, so RT60 = 646.8 ÷ 276.4 = 2.34 s.

Its panel plan adds 16 ceiling clouds of 4 by 4 ft (256 sq ft at 0.90, 230.4 sabins), 14 fabric wall panels of 2 by 4 ft (112 sq ft, net 0.75, 84.0 sabins) and 4 printed art panels of 4 by 6 ft (96 sq ft, net 0.75, 72.0 sabins). The total is 662.8 sabins and RT60 = 646.8 ÷ 662.8 = 0.98 s, inside the S04 dining limit of 1.0 s.

S05 is a different test. The clouds cover 256 of the 1,200 sq ft ceiling, about 21% before anything is subtracted for lights, well short of the 50% Tier 1 needs, even if suspended clouds count toward ceiling coverage at all. To reach Tier 1 the room would need at least 600 sq ft of qualifying ceiling treatment, more if less of the ceiling counts as available.

The example points to a planning habit. When a WELL project includes S05, size the ceiling treatment to S05’s coverage first and then check S04, because coverage rules can demand more area than the reverberation target alone would. In this room, 600 sq ft of ceiling treatment rated 0.75, counted at a net 0.70 over the painted gypsum it replaces, adds 420.0 sabins on its own: 646.8 ÷ (276.4 + 420.0) = 646.8 ÷ 696.4 = 0.93 s, inside the dining limit before any wall panel goes up.

The documents a panel supplier should provide

A WELL reviewer verifies S05 against a design specification and S04 against a model or a test, so the panel documents have to support both. Ask any supplier for the following, and expect the answers in writing.

  1. The test report behind every rating. For NRC, an ASTM C423 report with its edition, the mounting type under ASTM E795, the lab and the report number. For alpha-w, an ISO 354 report with the ISO 11654 rating.
  2. The rating for the product as installed. Thickness, core, facing, print and mounting should match the report. A ceiling product tested in a suspended mounting does not support a panel glued flat, and the reverse is also true.
  3. The full band table, not only the single number. A modeling report for S04 needs coefficients by frequency, and a single NRC hides how a panel performs at the low end.
  4. A coverage takeoff for each applicable room: available ceiling area, treated area, wall areas and percentages, keyed to the drawings.
  5. Drawings showing panel locations, sizes and mounting, so the reviewer can match the takeoff to the plan.
  6. Fire and emissions documents. These sit outside the Sound concept, but the building code asks about fire, and the WELL Materials concept and the project’s consultant may ask about emissions. List them by name and date.

How to write these requirements into a specification is covered in specifying acoustic panels, and the acoustic panel spec checklist turns them into questions to send. The NRC calculator recomputes NRC and SAA from a band table, a quick way to check a supplier’s rounding.

Fibson designs and makes acoustic panels to order and plans each room before anything is ordered. Its room plans name the core or fabric maker’s published report for every coefficient, with method, edition and mounting; Fibson has not yet tested its finished panels, and it makes no WELL compliance claim for its products. Architects and designers can request samples and spec sheets through design trade services.

Common submittal mistakes

Mistake Why it fails Fix
Quoting 0.5 s for an open office That is a WELL v1 number; v2 sets no open-office reverberation limit Cite the version the project is registered under
Using planning coefficients as ratings S05 thresholds apply to the product’s tested NRC or alpha-w Cite the test report for each product counted
A rating from the wrong mounting A suspended test does not support a flat-mounted panel, or the reverse Match the mounting in the report to the installation
Counting clouds or baffles without asking How suspended units count toward “available ceiling area” is not settled in the text we read Confirm with the WELL coach or IWBI before counting
Skipping the 10% test S04 and S05 apply only if listed room types reach 10% of occupiable area Run the area check at schematic design
Mixing NRC and alpha-w in one takeoff without saying so The two ratings can differ for one product Name the rating used for each product
Desk screens measured from the desktop The 4 ft height is “above finished floor” Check screen height against the floor

How owner standards use WELL: the Cornell example

Owners write WELL into their own standards, and those standards age at their own pace. Cornell University’s Design and Construction Standard 098000 Acoustics, dated January 2019, is a clear example.

Its list of codes and standards includes the “International WELL Building Institute Standard, Concept: Comfort, Features 74, 75, 78, 79, 80, 81.” Those are v1 feature numbers: exterior noise intrusion, internally generated noise, reverberation time, sound masking, sound reducing surfaces and sound barriers. A design team working on a Cornell project that is also pursuing WELL v2 has two sets of numbers to reconcile.

Cornell’s standard also shows what a mature owner adds on top of a rating system. It requires that acoustical standards be “verified through measurement during construction and the final commissioning phase,” names ISO 3382-2 for measuring reverberation, and calls for post-occupancy testing that confirms “the final NC, STIPA, and RT60.” It asks designers to “Specify acoustical ceiling tiles for a 0.75 NRC (minimum of 35 CAC),” and its sound masking guidance cites WELL design guidelines for a range of 45 to 50 dBA.

The lesson for specifiers is simple. When an owner standard and WELL both apply, list each requirement with its source and version, take the stricter of any two numbers that govern the same thing, and note where they measure different things, such as Cornell’s ceiling attenuation class, which WELL’s S05 does not address.

A WELL sound checklist for finishes

Work through these steps early in design, before finishes are locked. Most of them are a matter of reading the right version and keeping documents tied together.

  1. Confirm the version. Record the WELL version and date the project is registered under, and do not quote v1 or pilot thresholds for a v2 project.
  2. Run the 10% test. Add up the floor area of the room types listed in S04 and S05 and check whether they reach 10% of occupiable area.
  3. Label the zones. Prepare the S01 zone plan, and make the panel plan part of the S01 acoustic design plan.
  4. Choose the S04 pathway. Design for new rooms whose finishes are still open; performance for existing rooms or teams that prefer to measure.
  5. Model every applicable room with traceable coefficients, and state the frequency bands used.
  6. Pick the S05 tier. Tier 1 often follows from S04 compliance; Tier 2 needs full ceiling coverage at 0.90 and, in open workspaces, rated screens.
  7. Collect the documents. Test reports, band tables, takeoffs and drawings for every product counted.
  8. Check the owner standard, if there is one, and reconcile its numbers with WELL’s.

For rooms where reverberation is the main complaint, such as meeting rooms used for video calls, the room-level detail is in why your meeting room echoes on video calls. If you want a reverberation estimate, a panel layout and the supporting reports assembled for a WELL project, Fibson’s acoustic design service covers that, and the offices page describes how it approaches workplaces. Send the plans and room list through the contact form.